Enercept Fire Rating

 

This home, located in North Dakota, caught on fire while the owner was on vacation. The walls were constructed using Enercept Structural Insulated Panels; they used trusses for the roof. Although most of the home sustained extensive damage, the exterior walls remained standing with little damage.


before fire click on images to enlarge after fire

 

 

Enercept Wall Fire Rating

ASTM E119-98

FIRE TEST OF BUILDING CONSTRUCTION AND MATERIALS

OSB Panel Wall with Type X gypsum Wallboard Facing and EPS Foam core

Project Number 153-105934

One hour fire Resistance Test of a Bearing Wall Assembly.

February 8, 2000

Prepared for: Enercept, Inc., 3100 9th Ave. SE, Watertown, SD 57201

By: Omega Point Laboratories, Deggary N. Priest, President

Reviewed and approved: William E. Fitch P.E. Number 55296

 

ABSTRACT

A bearing wall assembly consisting of a base wall construction of 7/16 inch OSB facing over a 5-1/2 inch thick core of EPS foam and structurally supported with 2×4 wood studs located at each joint, with 2 layers of 5/8″ Type X gypsum wallboard applied to both sides of the wall, assembled and tested as described herein, successfully met the conditions of acceptance as outlined in ASTM Method E119-98 FIRE TESTS OF BUILDING CONSTRUCTION AND MATERIALS for a loadbearing fire endurance rating of 60 minutes.

 

Enercept Roof Fire Rating

ASTM E119-98

FIRE TESTS OF BUILDING CONSTRUCTION AND MATERIALS

OSB Roof/Ceiling Assembly with Type X Gypsum Wallboard Facing and EPS Foam Core.

Project Number 15345-105935

 

One hour Fire Resistance Test of a Roof Panel Assembly Under Unrestraied, Loadbearing Conditions.

February 13, 2000

Prepared for Enercept, Inc., 3100 9th Avenue SE, Watertown, SD 57201

By: Omega Point Laboratories, Deggary N. Priest, President

Reviewed and approved: William E. Fitch, P.E. Number 55296

ABSTRACT

A roof/ceiling assembly consisting of (5) pre-constructed sandwich panel sections, assembled in accordance with manufacturer’s instructions and tested as described herein, was tested in accordance with ASTM E119-98 FIRE TESTS OF BUILDING CONSTRUCTION AND MATERIALS under unrestrained, loadbearing conditions. The roof/ceiling assembly was tested under a superimposed live load of 30 pounds per square foot and achieved a fire resistance rating of 60 minutes.